Atlantis Solar Air Conditioner Installation
5. Empty the air in the insulating tank and indoor unit completely
If air, water or other impurity, which is mixed in the air conditioner system, will lead to the
working current exceedingly high, the capillary blocked, etc which will affect the
performance of the air conditioner. As a result, please eliminate air, water and other
impurity in the cooling pipe of insulated tank and side tube of indoor unit.
Empty the insulating tank
Please follow the instructions to eliminate the air in the insulating tank.
(As shown in the picture)
①Please adopt the wrench to dismount the A1 and the A2 cut-off valve bonnets of the
outdoor unit.
②Please adopt the wrench to loosen the stud type copper sealing appurtenance half a
circle upon the air pipe of A1cut-off valve.
③Please adopt the inner hexagonal wrench to loosen the center of A2cut-off valve for 90°.
After 7 to 11 seconds, fasten up the A2 cut-off valve. Air is exhausted from A1 air stud type
copper sealing appurtenance. When there is no air escaping, according to the moment
from 20 to 25N·M, please fasten the stud type copper sealing appurtenance.
④Please adopt the inner hexagonal wrench to open the A1 and A2 cut-off valve cores.
⑤Please fasten A1 and A2 cut-off valve bonnets.
⑥Please adopt soapy water or halogen detection instrument to detect leakage. If you find
leakage, you need to fasten A1 and A2 cut-off valve bonnet. And then you can adopt